With their long-lasting modular and compact design, the self-contained units provide easy application and maintenance possibilities, offering ideal solutions for various applications. This allows businesses to use these units efficiently, enhancing their overall performance. Thanks to their modular structure, they can quickly adapt to different spaces and requirements, making them versatile and practical for various uses.
Cooling capacity.
Ambient temperature range for operation.
“Tailor Made Solutions” designed and produced according to your needs.
Environmentally friendly gases with low global warming impact.
Durable design against vibration.
Dust and corrosion resistant design.
| Technical Specifications | ISCA | Unit | ISCA 50 | ISCA 70 | ISCA 100 | ISCA 175 | ISCA 260 | ISCA 350 | ISCA 420 | ISCA 525 | ISCA 620 | ISCA 700 | ISCA 860 | ISCA 1050 | CUSTOMIZED |
| Cooling Capacity | kW | 5,62 | 7,44 | 9,76 | 19,00 | 27,81 | 38,00 | 45,21 | 55,62 | 62,73 | 74.00 | 91,67 | 107,14 | 120,00 |
| Power Consumption | kW | 2,62 | 3,53 | 4,46 | 6,83 | 10,06 | 13,75 | 17,73 | 19,57 | 22,70 | 27,72 | 31,38 | 39,21 | |
| Capacity Control | % | N/A | N/A | N/A | N/A | N/A | %50-100 | %50-100 | %50-100 | %50-100 | %50-100 | %50-100 | %50-100 | |
| Condenser Unit | Type | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | Air Cooled-Copper Tubes/Aluminium Fins | |
| Max. External Air Static Pressure | Pa | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | 250Pa/500Pa(optional) | |
| Nominal Air Flow Rate | m³/h | 1.250 | 2.000 | 2.500 | 3.500 | 5.000 | 7.000 | 8.500 | 10.000 | 12.500 | 15.000 | 18.000 | 21.000 | Contact Us |
| Air Filter / Class | Type | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 | Cassette type / EU4 |
| Dimensions - SCU Unit (WxDxH) | mm | 930x560x1.580 | 930x560x1.580 | 930x560x1.750 | 930x560x1.750 | 1.235x770x2.080 | 1.235x770x2.080 | 1.435x920x2.250 | 1.435x920x2.250 | 2.000x1.200x2.490 | 2.000x1.200x2.490 | 2.000x1.200x2.490 | 2.150x1.400x2.810 | |
| Dimensions - Condenser Unit (WxDxH) | mm | 993x743x819 | 993x743x819 | 993x743x819 | 1.463x895x815 | 1.578x892x819 | 1.463x900x819 | 1.613x900x819 | 1.578x892x819 | 1.813x1.045x819 | 1.813x1.045x819 | 2.513x1.045x819 | 2.513x1.044x819 | |
| Net/Gross weight - SCU Unit | kg | 280/340 | 280/340 | 290/350 | 330/390 | 450/510 | 510/590 | 600/760 | 610/690 | 735/825 | 1.100 / 1.200 | 1.250 / 1.350 | 1.450 / 1.550 | |
| Net weight - Condenser Unit | kg | 50 | 50 | 60 | 85 | 90 | 2x100 | 2x110 | 2x120 | 2x125 | 2x175 | 2x180 | 2x180 | |
| Power Supply | V/Ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 | 400/3/50 |